FZN21-12 and FZN21-12(R)D Series indoor AC HV load switch with fuse
FZN21-12 Series Indoor High Volgate Break Switch
1 ISO9001:2000
2 12KV
3 Safty,Perfect,Loss energy loss
Overview
FZN21-12D/T630-20, FZN21-12DR/T125-31.5 Model and composition of high-voltage vacuum load switch for three-phase AC electrical 12kV, 50Hz power distribution system, with a compact, small size, light weight, long life Closing breaking ability, safe and reliable, and fuse with the use of (the combination of electrical appliances), to replace fuses with higher cost, its operating and maintenance easy and convenient.maintenance.
FZN21-12-Model load switch and the combination of electrical appliances mainly by frame, isolating switch (or fuse charging separate switch), vacuum interr../upter, grounding switch, operating mechanism and other components.
This product is compact, small size, long life, customs co-breaking ability, easy operation and maintenance. Vacuum switch operating mechanism and distribution and electricity storage spring, the CO can be fast operation. Isolation switch, vacuum switch, grounding switch interlock each other in order to prevent misuse.
Main technical parameters
Serial number | Project | Unit | Parameter | |
FZN21 | FZRN21 | |||
1 | Rated voltage | KV | 12 | 12 |
2 | Rated Current | A | 630 | 125 |
3 | Rated short circuit making current | kA | 50 | 50 |
4 | Rated short-circuit breaking current (Switchgear) ) | kA | —— | 31.5 |
5 | Rated active load breaking current | A | 630 | 630 |
6 | 4Sthermal current | kA | 20 | —— |
7 | Dynamic current | kA | 50 | —— |
8 | 1min power frequency withstand voltage | kA | 42(Fracture48) | 42(Fracture48) |
9 | Lightning impulse withstand voltage | kA | 75(Fracture85) | 75(Fracture85) |
10 | Mechanical life | Times | 10000 | 10000 |
11 | Rated transfer current (Switchgear) | A | —— | 3150 |
12 | Motor operating voltage | V | AC-DC110,220 | AC-DC110,220 |